Product Details

INFS0812 Intumescent Strip / SSCI Firestop Collar

  • Model:INFS0812

    Product Introduction

    Description:

    INFS0812 Intumescent Strip is a proprietary fire retardant flexible
    strip bonded on one side to aluminum foil.

    SSCI Firestop Collar is a stainless steel collar intended to be used in
    conjunction with INFS0812 Intumescent Strip to tightly seal any
    opening that is created as a material is consumed by fire. This combination
    will restore the fire resistance rating of walls, floors and seals against the
    passage of
    flames, toxic fumes and smoke. INFS0812 Strip and SSCI Collar
    are designed to make installation quick and easy.

    Uses:
    INFS0812 can be used on any through-penetration items. SSCI can be used on
    plastic or nonmetallic pipes.

    Feature:

    ●Proprietary intumescent properties
    ●Quick expansion rate efficiently seals
    ●all gaps Can be cut to fit to any size or shape to fit irregular openings

    Specification of INFS0812:

    Standard size 5mmx60mmx2M
    Expansion rate ≧20 times
    L.O.I. ≧40

    Environmental exposure tests  
    (As per UL1479 request)

    ●Accelerated aging (158 5 F for 270 days) pass
    ●High humidity (97-100%RH & 95 3 F for
      180days) pass

    Test:

    ●UL1479, 3hrs, T Rating and F Rating
    ●ULC S115 2hrs FTH Rating
    ●FM approved
    ●CNS14514, 3hrs, Class A and B
    ●GB23864
    ●ASTM E662

    Installation guide:

    1. Release hose clamp screw and disassemble the SSCI-X Firestop Collar.

    2. The required number of layers of wrap strip are individually and tightly wrapped around
        each nonmetallic through
    penetrant and secured together by means AL-foil tape.

    3. Wrap strip shall be butted against floor bottom or both surfaces of wall.

    4. Collar shall then be wrapped around the outer circumferenceof the wrap strip and
        secured with a steel hose clamp (for  collar width 120mm, use 2 hose clamps).

    5. Secure collar to floor bottom or wall on both sides of opening by means of 1/4-20
        concrete wedge anchors in accordance
    with installation instructions.

    6. One anchor shall be placed through each mounting bracket of the collar.

     Specification of SSCI:

    Nominal size of pipe2”3”4”5”~6”7”~8”9”~12”
    Intumescent strip layers122334
    Collar width(mm)6060606080120
    Number of fixing tabs334668