Product Details

FP-02 Firestop Sheet

  • Model:FP-02 Firestop Sheet

    Product Introduction



    Description:

    FP-02 Firestop Sheet is fabricated by bonding proprietary intumescent materials to a metal sheet.
    INCA Firestop Sheet is specifically designed to protect large penetration openings on fire
    rated walls and floors.

    Firestop sheet securely blocks flame and prevents the passage of toxic fumes and smoke.
    After exposure to 1x10⁶ Gy (1x10⁸ rad) of neutron or gamma radiation, FP-02 will
    maintain full firestop performance
    characteristics 50 plus years.

    Uses:

    Firestop sheet closes large penetration openings
    on walls or floors. Used to protect cables, cable
    trays, piping, conduit andpenetrations of busway
    consisting of a variety of materials.

    Firestop sheet can be installed with other
    proprietary products such as Firestop Putty,
    Fire Barrier Sealant or Intumescent Strips.

    Feature:

    ●Easily trimmed to different sizes to fit any
      installation

    ●Fits large openings and works with nearly
      all construction materials
    ●Halogen free
    ●Asbestos free
    ●Stable and maintenance free

    Specification:

    Size                   90cmX90cm
    Thickness           7.7± 1.3mm
    Expansion rate    ≥5 times

    Test:

    ●UL1479, 2hrs, F Rating
    ●FM approved
    ●CNS14514, 2hrs, Class A& B
    ●GB23864
    ●ASTM E84
    ●ASTM E662

    Installation guide:

    1. Apply INCA Firestop Putty FM012 or INCA Fire Barrier Silicone Sealant INSS2460 around the perimeter of the opening. 

    2. Firestop Sheet to be installed to lap a minimum of 2 in. (51mm) on all sides of
        the through opening and with the
    aluminum foil facing against the surface of the
        floor (galvanized steel plate side outwards). 

    3. Sheet to be secured to the top surface of floor using min 3/16 in. diam by 1-1/2 in.
        (5 mm by 38 mm) long steel
    expansion bolts in conjunction with min 1-1/4 in.
        (32 mm)
    diam steel fender washers.
        Max spacing of fasteners not to
    exceed 6 in. (152 mm) OC.

    4. All wall openings require a cover sheet of FP-02 Firestop Sheet
        and putty/sealant on both sides of the wall.